产品型号、规格及编号 Product specification  
| 产品名称 Name | 
型号规格Type | 
适用电缆截面Section |  
10kV户内交联三芯终端 10kV indoor cross-linking three-cores terminal    | 
NSY-10 / 3.1 | 
25-50 |  
| NSY-10 / 3.2 | 
70-120 |  
| NSY-10 / 3.3 | 
150-240 |  
| NSY-10 / 3.4 | 
300-500 |  
10kV户外交联三芯终端 10kV outdoor cross-linking three-cores terminal | 
WSY-10 / 3.1 | 
25-50 |  
| WSY-10 / 3.2 | 
70-120 |  
| WSY-10 / 3.3 | 
150-240 |  
| WSY-10 / 3.4 | 
300-500 |  
10kV户内油浸三芯终端 10Kv indoor oil-dipped three-cores terminal | 
NSZ-10 / 3.1 | 
25-50 |  
| NSZ-10 / 3.2 | 
70-120 |  
| NSZ-10 / 3.3 | 
150-240 |  
10kV户外油浸三芯终端 10Kv outdoor oil-dipped three-cores terminal | 
WSZ-10 / 3.1 | 
25-50 |  
| WSZ-10 / 3.2 | 
70-120 |  
| WSZ-10 / 3.3 | 
150-240 |    产品技术指标 Product technical index  
| 项目Item | 
  | 
试验项目 Test item | 
标准要求 stand requirement | 
试验结果 Result | 
详注 Note |  
10kV户内户外终端 10kV indoor outdoor terminal | 
1 | 
工频电压试验(湿态) | 
45kV,1min 不闪络、不击穿 | 
45kV,1min,组合试样各项均未闪络和击穿 | 
符合要求 |  
| 2 | 
局部放电试验 | 
13kV下放电量不大于20pC | 
13kV下组合试样各项放电量均为5pc | 
符合要求 |  
| 3 | 
负荷循环试验 | 
导体加热至(90-95℃,每一循环为8h,其中加热5h,冷却3h,共循环3次) | 
按标准要求完成3次负荷循环试验 | 
由以下试验评定 |  
| 4 | 
局部放电试验 | 
13kV下放电量不大于20pC | 
13kV下组合试样各项放电量均为5pc | 
符合要求 |  
| 5 | 
冲击电压试验 | 
105kV,正负极各10次不闪络,不击穿 | 
105kV,正负极各10次(见附录A),组合试样各项均为闪络和击穿 | 
符合要求 |  
| 6 | 
负极性直流电压试验 | 
52kV,15Min,不闪络不击穿 | 
52kV,15Min,组合试样各项均为闪络和击穿 | 
符合要求 |  
| 7 | 
工频电压试验 | 
35kV,4h,不闪络不击穿 | 
35kV,4h组合试样各项均为闪络和击穿 | 
符合要求 |    |